Sources are plugins — the built-in ones follow the same contract as custom plugins. Bricklogger comes with one, BACnet/IP; other sources are installed as plugins, such as the iBOS source for the iBOS Data API, and document themselves. Every source declares which collection methods it supports; poll exists for all sources.

BACnet/IP

The first version's source. Its collection method is poll: the points are read at the rule's interval. Change of Value (COV), where the source subscribes to changes on the device instead of polling, follows in a later version as a method of its own.

A BACnet read carries no time, so the source stamps every observation itself with the machine's clock when the response is received.

Read only

Bricklogger never writes to a BACnet device. The only services it sends are Who-Is, ReadProperty and ReadPropertyMultiple. There is no WriteProperty, no WritePropertyMultiple, no SubscribeCOV, no ReinitializeDevice and no time synchronisation, neither in the daemon nor in any of the protocol tools, and the source contract has no way to express a command: a source is handed points and returns observations. No rule can be written that changes anything in the building, because the rule schema has nothing to write with.

The instance is itself a BACnet device on the network, with a device object and a network port object, so that it can be found and addressed like any other. It answers WriteProperty to its own two objects, because the protocol stack it is built on serves that service, and it exposes no commandable points: there is no present value and no priority array anywhere in it, so nothing in the building can be driven through Bricklogger. What another device can reach that way are the logger's own settings, such as its APDU timeout and its retry count.

Configuration

# sources.yaml
bacnet_main:
  type: bacnet-ip
  address: 192.168.10.5/24        # required: local address with prefix length
  device_instance: 1200           # required: the instance's own device object
  device_name: bricklogger-main   # default: the instance name
  vendor_id: 999                  # default: 999 until a vendor identifier is assigned
  devices: ["1000-1999", 2500]    # optional: claim scope by device instance
  subnet: 192.168.10.0/24         # optional: claim scope by the graph's IP
  bbmd:                           # optional: register as a foreign device
    address: 10.0.0.1
    ttl: 60s
  timeout: 3s                     # default
  retries: 2                      # default
  max_in_flight: 8                # default: requests on the wire at once
Key Requirement Content
address required The local IPv4 address with prefix length, e.g. 192.168.10.5/24; the prefix gives the broadcast address. A port other than 47808 is appended: 192.168.10.5/24:47809
device_instance required The number of the instance's own device object. It must be unique on the BACnet network, so there is no default
device_name optional The name of the instance's own device object; default the instance name
vendor_id optional The vendor identifier the instance's own device object reports. Vendor identifiers are assigned by ASHRAE; the default 999 stands in until Bricklogger has one of its own
devices optional The device instances the instance claims: a list of numbers and ranges written "low-high"
subnet optional The instance claims only devices whose IP in the graph lies in the subnet; a device without an IP in the graph is then not claimed
bbmd.address optional A BBMD to register with as a foreign device, for broadcast discovery across routers
bbmd.ttl default 60s How often the registration is renewed
timeout default 3s How long a request waits for an answer before a retry
retries default 2 Retries per request before the read counts as failed
max_in_flight default 8 How many requests the instance may have on the wire at once, across every device and every search

A device is in scope when it satisfies every restriction given. Without devices and subnet the instance claims every device with a BACnet reference — the simple installation configures nothing. The exclusive resource the instance declares is udp:<address>:<port>, so two instances on the same socket are caught at validation.

The reference

A point is addressed through Brick's external reference: the point carries ref:hasExternalReference to a reference node, and the source accepts that node in its property form:

ex:AHU_01_SAT a brick:Supply_Air_Temperature_Sensor ;
    ref:hasExternalReference [
        a ref:BACnetReference ;
        bacnet:object-identifier "analog-input,3" ;
        bacnet:objectOf ex:AHU_01_Controller ;
        ref:read-property "present-value"      # optional; this is the default
    ] .

ex:AHU_01_Controller a bacnet:BACnetDevice ;
    bacnet:device-instance 1201 ;
    bacnet:hasPort [
        a bacnet:Port ;
        bacnet:ip-address "C0A80A14"^^xsd:hexBinary   # optional; 192.168.10.20
    ] .
  • The object: bacnet:object-identifier names it as type,instance with the standard's hyphenated type names, e.g. analog-input,3 or multi-state-value,12. The literal may be plain or typed bacnet:objectIdentifier. The source recognises a BACnet reference by this property, whether or not the node is typed ref:BACnetReference — Brick's own example leaves the type to inference.
  • The device: reached through bacnet:objectOf or bacnet:contains; Brick's example uses the first and its shape the second, so the source accepts both. Two BACnet vocabularies occur in models, http://data.ashrae.org/bacnet/2020# in the bundled Brick and http://data.ashrae.org/bacnet/ in Brick's current schema, and the source accepts both. The device node must carry bacnet:device-instance. A port with bacnet:ip-address is optional and is used as a hint when finding the device.
  • The property: ref:read-property names the property to read and defaults to Present_Value. Any readable property can be named, e.g. reliability or out-of-service, in the standard's hyphenated spelling or as the ASHRAE vocabulary's IRI — both forms occur in models. Array elements cannot be addressed in the first version.
  • bacnet:object-name, bacnet:description and bacnet:units on the reference are informational and play no part in addressing.

The source reads the reference, the device and its port from the graph itself with the read-only SPARQL access every source has; the daemon hands over nothing about references.

What is rejected. A reference the source recognises but cannot use gives the point the outcome rejected with a reason that names the problem, and the point is not collected until the model is fixed. That covers the URI form (ref:BACnetURI), a reference with only an object name, a malformed object identifier, a device node without bacnet:device-instance, a bacnet:object-type that contradicts the type in the identifier, an unknown property name, and a point with two BACnet references of which neither is marked ref:preferred true — where one is marked, it is used. The rule is one: a reference that is not complete and unambiguous is not read, because a point logged from the wrong object under the right name is worse than a visible gap.

Finding the device

The source finds a device on the network by its device instance with Who-Is; an address from the graph is a hint, never the truth:

  • If the graph carries an IP for the device, a unicast Who-Is goes to that address first. The I-Am confirms that the instance lives there, no broadcast is needed, and it works across subnets.
  • Otherwise — or if the hinted address does not answer — a broadcast Who-Is for that instance goes out on the local network, or through the BBMD in the instance's configuration. An instance bound to a single address without a network, a /32, has no broadcast address and reaches only devices the graph gives an IP.
  • The address that answers is cached and looked up again when the device stops answering, so a device that is re-addressed comes back by itself. Devices behind BACnet routers are reached through the routed address their I-Am carries.

Polling

The source owns the rhythm, and what it puts on the network is bounded. A logger on a building's own network must never be the reason something else stops answering:

  • Points on the same device with the same interval are read together in one ReadPropertyMultiple, so they share one request and one timestamp. A device that does not support it is read with ReadProperty, one property at a time.
  • One outstanding request per device and interval. Within a round the requests follow one another; a device whose points are accepted at two different intervals is polled by two rounds, which can overlap.
  • At most max_in_flight requests are on the wire at once, counted per instance and whatever the number of devices; the default is 8. Everything the instance sends passes that ceiling, the searches included, so a network never sees more of Bricklogger's requests at a time than the number configured. It is the setting to lower on a fragile network or one where everything sits behind a single router.
  • First rounds are spread over the interval, at most a minute, so a rule with hundreds of devices does not start them all in the same instant. Each device keeps its offset afterwards, so the load stays even instead of gathering at every interval boundary.
  • Reads never pile up. If a device's round is still running when the next is due, the next round is skipped. Skipped rounds are counted per device in status, and a device that keeps missing its interval gets the warning poll_overrun. The interval is thus a minimum, and every observation carries the time it was actually received, so a device that cannot keep up is visible both in status and in the time series.

Value types and units

The value type follows the datatype of the property as read, not the object type alone, because ref:read-property can name any property. For a standard property the datatype is known from the standard before the first read; for a proprietary property it is the datatype of the first successful read.

BACnet datatype Value type Texts and notes
REAL, DOUBLE number Analog objects, Large_Analog_Value, Loop. NaN and infinity become null with reason no_value
Unsigned, INTEGER integer Integer_Value, Positive_Integer_Value, Accumulator
BOOLEAN boolean e.g. Out_Of_Service
Present_Value of a binary object boolean active is true; texts from Active_Text and Inactive_Text when the object has them
Present_Value of a multi-state object enum The ordinal is BACnet's own value, counting from 1; texts from State_Text
ENUMERATED elsewhere enum e.g. Reliability; the ordinal is the enumeration value, the texts are the standard's names
CharacterString string
DateTime datetime BACnet's DateTime carries no zone; it is read as the machine's local time and stored in UTC, since device and logger share a building
BitString, OctetString, ObjectIdentifier, Date or Time alone, lists and structures — The point is rejected: the datatype has no counterpart in the vocabulary

Bit strings are not a type, and with the property form a single bit cannot be addressed, so there is nothing to decompose them into. A status word that is wanted as a time series is modelled as its own boolean points where the device offers them.

Units. The protocol's unit is the object's Units property, one of BACnet's engineering units. The source translates it into Brick's unit vocabulary (QUDT) where the standard's unit has a counterpart — degrees-celsius to unit:DEG_C, kilowatt-hours to unit:KiloW-HR and so on — and otherwise delivers the BACnet name itself, e.g. a proprietary unit as proprietary-<number>. no-units, and objects without a Units property, give no protocol unit. As for every source, the graph's unit stays primary, a disagreement gives the unit_conflict warning, and values are never converted.

When metadata is read. Units, State_Text, Active_Text and Inactive_Text are read once when a point is assigned and delivered as the point's metadata. For a point that reads another property than Present_Value, the value type and the enumeration's texts follow the first successful read. Metadata is read again whenever the device has been rediscovered after being unreachable, since a device may have been reconfigured while it was gone.

Status flags

Every BACnet object carries four status flags. When Present_Value is read, the source maps them to observations as follows; a rule that reads another property, such as Reliability, gets that property's value whatever the flags say, because logging the status is what such a point is for:

Flag Observation
IN_ALARM The value is delivered unchanged
FAULT null with reason fault
OUT_OF_SERVICE null with reason out_of_service
OVERRIDDEN null with reason overridden

The status flags are read together with the value. If the status itself is to be logged as a time series, it is modelled as its own point in the graph: Brick's BACnet reference can, with ref:read-property, point at e.g. Reliability or Out_Of_Service instead of Present_Value.

Failed reads

If the device does not answer — timeout or offline — every poll attempt yields null with reason unreachable, and so does every attempt before the device has been found on the network. If it answers with an error — unknown object, unknown property, access denied — the attempt yields null with reason read_error.

A device that has been lost is looked for again with a Who-Is, but not on every round. The search backs off: the first retry after 30 seconds, then doubling to at most 5 minutes, and the count resets the moment the device answers. A search that finds nothing at the address the model gives has to broadcast, which every device on the network must process and which a BBMD forwards to other subnets, so a controller switched off for a working day must not become a broadcast every few seconds. The points keep yielding unreachable at their own interval while the search waits, so status and the time series are unchanged by the backoff; only the searching is.

Protocol tools

The tools run with bricklogger sources bacnet-ip <tool> — through the daemon when it runs, in-process otherwise — as described for protocol tools in general. Every tool returns a structured result that the CLI renders as a table or emits as JSON.

Tool Parameters Result
discover --low and --high bound the device instances asked for (default: all); --duration is the listening time (default 3s); --address sends the Who-Is to one address instead of broadcasting, for an interface without a broadcast address or a device or BBMD on another network The devices that answered: instance, address, name, vendor and model
read --device as instance number or address, --object identifier, --property (default present-value), --index for an array element The value as the vocabulary sees it, BACnet's own datatype and the status flags; an error the device answers with is returned as error
objects --device; --values adds Present_Value and Units The device's object list: identifier, name and type, optionally value, unit and its QUDT counterpart
resolve --point, a URI in full or prefixed form How the point's reference resolves — device instance, the address found, object and property, whether the device is in the instance's scope — and the value with its status flags, or the problem with the reference
pointlist --device for one device, in scope or not; --low and --high bound the search as for discover; --values adds each object's Present_Value The point list: the devices the instance claims, or the one device, with the objects on each, as one JSON document to keep as a file

discover, read, objects and pointlist need nothing but the instance's configuration, so they also run without a daemon; a device given by instance number is found with a Who-Is, so on an interface that cannot broadcast it is given by address. resolve needs the running daemon, because the working graph is the daemon's; without one the command says so plainly, like status and points. It is the shortest path from a warning in status to its cause.

No tool writes to a device. The first version reads only.

The point list

The point list is what the network has, without a single sample: the devices in the instance's scope and the objects on each — an inventory to file with the building's documentation, or to hand to whoever builds the Brick model. On a BACnet site there is rarely another one. It is a document, so the CLI writes it as JSON, to standard output or to a file with -o:

bricklogger sources bacnet_main pointlist -o building-a.json

In the web interface it is offered on the discover listing: run discover, and every device row carries a Download for that device's point list, with a Download for the whole list above the table. The tool has no form of its own there.

Without arguments the list covers the devices the instance claims, so the Who-Is is bounded by the devices ranges and the answers are filtered by devices and subnet both. --low and --high widen or narrow the search deliberately, as they do for discover, and --device covers one device whether or not the instance claims it. --values adds each object's Present_Value, which costs one more reading per object.

{
  "instance": "bacnet_main",
  "address": "192.168.10.5/24:47808",
  "exported_at": "2026-09-15T13:05:12+00:00",
  "counts": {"devices": 1, "objects": 2},
  "devices": [
    {
      "instance": 1201,
      "address": "192.168.10.20",
      "name": "AHU-01 controller",
      "vendor": "Siemens",
      "model": "PXC36.1-E.D",
      "objects": [
        {"type": "analog-input", "instance": 3, "name": "AHU01_SAT", "unit": "degreesCelsius", "qudt": "http://qudt.org/vocab/unit/DEG_C"},
        {"type": "binary-input", "instance": 1, "name": "AHU01_FAN", "unit": null, "qudt": null}
      ]
    }
  ]
}

The header names the instance, its own address, the time of the export in UTC and the counts; then follow the devices, each with its objects. The fields are those of discover and objects, so the document reads as the two lists nested. A device that stops answering halfway through is kept with the objects it managed to give and an error beside them, because half a site's inventory is worth more than none.

It asks one thing at a time. The sweep is one Who-Is, then per device one read of the object list and one ReadPropertyMultiple per twenty objects, with never more than a single request outstanding. A whole site therefore takes a while and puts no more on the network at any instant than one poll round does, which is why it needs no ceiling of its own.

Which points the source serves

A source instance claims the points whose external references it can reach. It finds the references of its type in the Brick graph itself, through the read-only SPARQL access every source has, and decides the claim from its own configuration — address, subnet, device range — without touching the network, so the binding can be shown and validated before collection starts. If there is no network restriction in the configuration, the instance claims all points with a reference of its type. If several instances claim the same accepted point, that is a validation error; if none does, the point is not collected and status warns. The source may query the graph at any time, and every model activation binds it anew, so it resolves its references again against the new model. The mechanics and the arbitration are described in the architecture.

What a source delivers

A source pushes observations up into the daemon — point, timestamp, type and value. The timestamp belongs to the source: the daemon never stamps anything itself. If the protocol carries no time, the source stamps with the machine's clock when the response is received; if the source receives timestamped samples, it passes the sample's timestamp on. Timestamps are always timezone-aware and in UTC, and a plugin that passes on device time must say so in its documentation.

A source only delivers a value it can vouch for as the point's value. If the device itself disputes the value, or the read fails, the source delivers null with a reason from the closed reason vocabulary in the architecture. Every poll attempt of a live source thereby yields exactly one observation. A history source, which copies samples the system has already recorded, delivers nothing for a failed request and fetches the stretch when the next one succeeds; the iBOS source is one.

In addition the source delivers point metadata for what only the protocol knows: the value type, the state texts for enum, the texts for boolean and the protocol's own unit designation — translated into Brick's unit vocabulary (QUDT) where possible, otherwise as the protocol's own designation. The source never converts values. Both vocabularies are closed and defined in the architecture; a source cannot add its own types or fields, but must map its protocol's values into the set.

For every assigned point the source reports an outcome on the status channel — active, unsupported or rejected with a reason — initially and whenever it changes. The daemon applies the rule's fallback on unsupported.

The source never talks to the destinations. It knows neither their number nor their kind.